CRYSTAL QUEST®  30,000 GPD Reverse Osmosis System

Detailed Description

 

Membrane: Twenty 4" x 40" TFC HF1 Membranes

Membrane Housing: 4" x 80" Membrane Housings

Pump & Motor: Grundfos 5 HP Motor and Stainless Steel Pump

Frame: Aluminum White Powder Coated Frame

Bag Filter: 32” Rosendale Bag Filter, 10 Micron Filter

Cartridge Filter: 2.5" x 40" 5 Micron Sediment Filter

Chemical Injection: Pulsafeeder 30 Gallon Chemical Feed System

Pressure Gauges: 2.5" Gauge, 0-300 PSI, Panel Mount Glycerin Filled, and 1.5" Gauge, 0-160 PSI, Top Mount, Dry Gauge

Low Pressure Switch: Square D Low Pressure Switch

Solenoid Valve: Solenoid Valve with Manual Override

Computer Controller: Rotrol S-150 Computer Controller, 220 volts AC, single phase, with built-in TDS monitor - pre-treat lockouts, tank full contacts, magnetic motor starter, low pressure monitoring, and alarms.

Flow Meters: One Product (0-20 GPM) & One Waste (0-20 GPM) Flow Meters

Easy Maintenance & Operation: CRYSTAL QUEST® commercial reverse osmosis systems feature a compact design and have all of their components strategically located for easy access and inspection.

 

Optional Features
 
Stainless Steel Housings: Ten 4” x 80” Puro Tech Stainless Steel Membrane Housings, 1/2” FNPT
 
High Pressure Switch: One Square D High Pressure Switch, Automatically starts when the tank pressure falls below 40 psi, and stops when the pressure reaches 60 psi.
 
Auto Flush: This feature will flush the systems membranes with the feed water, thus extending membrane life.
 
Float Switch: One Mechanical Float Switch, For atmospheric storage tank applications.
 
Concentrate Re-Circulate w/ 0-10 GPM Flow Meter: This feature offers a higher recovery rate for the system by taking a percentage of the waste water and feeding it back into the system.
 

System Specifications

Operating Specifications

Design

Horizontal

Gallons Per Day

30,000 @ 77 F

Dimensions (Approx.)

41" x 143" x 80"

Weight (Approx.)

NA

Concentrate Re-Circulate

Optional

Auto Flush

Optional

Element Size (in.)

4040 TFC HF

Elements (Qty.)

20

Motor HP

5

Voltage

110 or 220 Volts AC

Hertz

60 or 50 cycle

Feed Connection

2"

Product Connection

1.5"

Waste Connection

1.5"

 

Minimum Feed Pressure

35 psi

Minimum NaCl - % Rejection

96%

Minimum Feed (GPM)

30

Maximum Hardness

15 Grains / Gallon

Maximum TDS

2000 ppm

Operating Pressure

150 psi

Maximum NaCl - % Rejection

98.5%

Maximum Feed (GPM)

50

pH Range

3 - 11

Maximum Temperature

1050 F

 
  • Additional cost will apply to listed price for custom modification based on water laboratory test report.
 

Policies | Copyright | Legal CRYSTAL QUEST®